>You are currentlt in:Home > Fan coil unit > Concealed horizontal fan coil unit
Concealed horizontal fan coil unit
Product Type:Concealed horizontal
Place of origin:ChinaModel NO:FP
Product Information

Jetex-lloyd's fan coil unit is the ideal terminal widely applicable for central air conditioning system in hotel, office building, hospital and exhibition hall etc. It absorbs the advantages of domestic and foreign similar products, through elaborate design, and is manufactured by means of advanced processing technology. This product has beautiful appearance, compact structure, low noise and large cooling capacity and has won high appraisal from customers for many years.
The fan coil mainly consists of fan, heat exchanger (coil), overall die condensate tray and housing etc. The fan is air dual-inlet centrifugal fan, through strict dynamic and static balance test, and equipped with low noise 3-speed air conditioning motor and import ultra-low-noise rolling bearing with low energy consumption and good speed regulating performance. The coil is manufactured by using the most advanced production equipment of Japan and uses copper tubes in staggered arrangement, aluminum fins with flanged edge and fully automatic mechanical expansion pipes that can ensure close contact and high heat transfer efficiency. All models and associated variants of this series of products have obtained national refrigeration equipment production license.


How to order
1,The unit’s model. Type and direction of water inlet/outlet pipe must be described.(The method of judging the direction of water inlet/outlet pipe: face air outlet)
2,For special requirements of customer, please specify them during the order.


Fan Coil Unit features:
1, Exquisite Structure, pleasing in appearance, reasonable product structure, fire insulation.
2, It has the fine design, light weight and good strength,also easy installation.
3,The effiency is high. Fan coil adopt seamless red Copper Pipe and aluminum blinds-fin . Mechanical expand tubes make sure the Close contact between fin and cooper pipe,reaching he best heat transfer.Before leaving factory strict test is done, so is the 100% pressure leak testing (20 kg/cm2 pressure leak test), to ensure product quality and performance.
4, It is easy to control and owns complete functions.
5.Ceiling Exposed, Ceiling Concealed, Floor Mounted, Cassette type for optional.
6.Performance parameters like cooling and  heating capacity are measured in the following conditions:
Measured conditions Cooling capacity: dry ball 27, wet ball 19.5
inlet temperature 7. Measured conditions of heating capacity: dry ball 21, inlet temperature is 60.

Item\Model FP-200 FP-300 FP-400 FP-500 FP-600 FP-800 FP-1000 FP-1200 FP-1400
Standard Air Volume(m3/h) H 360 530 700 880 1020 1360 1720 2040 2400
M 270 400 530 660 765 1020 1290 1530 1800
L 180 265 350 440 510 680 860 1020 1200
Cooling capacity(w) 1900 2800 3700 4660 5400 7200 9100 10800 12670
Heating capacity(w) 2850 4200 5550 6990 8100 10800 13650 16200 19000
Static Pressure(pa) S 12 12 12 12 12 12 12 12 12
E 30 30 30 30 30 30 30 50 50
Noice Level(A) S ≤37 ≤39 ≤41 ≤43 ≤45 ≤46 ≤48 ≤50 ≤52
E ≤39 ≤41 ≤43 ≤45 ≤47 ≤48 ≤50 ≤52 ≤54
Coil Type Copper Tubes Aluminium Louver Fins
Water Flow(1000kg/h) 0.34 0.50 0.66 0.81 0.96 1.28 1.61 1.92 2.18
Pressure Drop(kpa) 6.0 7.2 14.0 24.0 32.0 16.0 18.8 23.0 28.0
Max Working Pressure 1.7
Motor Type   Sigle Phase Capacitor Motor
Power Supply   220V 50HZ
Power Input S 36 46 62 76 90 110 150 180 210
E 44 54 70 85 105 145 170 240 250
Quantity 1 2
Fan Type Air Dual-inlet Centrifugal Fan
Quantity 1 2 3 4
Pipe Connection 3/4"
Drain Pipe 3/4"